RCP
(A-10301)
Lighting:
In lighting selection, ensure the size of the lighting fixture above the ceiling does not exceed 7-8 cm.
Ensure that the strip light is continuous and not interrupted by any objects or obstructions that cause it to appear, stop, and then appear again
The LED should be concealed, with the main goal being that the light source is not visible.
Ceiling:
Width of ceiling groove for AC supply depends on length of the AC Supply and also on AC linear requirements which means 1 slot is equal to 2.5cm to 3 cm, 2 slots is equal to 5cm to 6cm.
Avoid having AC supply in cove including a curtain.
Standard size of ceiling Access Panels are 60x60cm square.
If sigma parapet, use 3mm thick rust-free aluminum sheet (pre-fabricated and powder coated flashing – double purpose)
All windows must include drip moulds.
Avoid spotlights in coves where there are curtains.
Avoid having spots too close to the walls
RCP:
We can use woven wire drapery as a replacement for grating mesh in basement parking; grating mesh remain option 1.
Staff Bedroom:
Keep 5 cm in front of a window, and locate the curtain's location.
Keep 90 cm in front of the wardrobe.
Use a bigger bed block wider than 90 cm.
General Notes:
The hood should be designed for 3000 CFM, with a duct size of 1x1 meter.
Study curtains in all spaces
HVAC SUPPLY 5CM GAP IN CEILING:
Conclusion of a meeting with E. Romeo, Ridhima, Walid, M.Salah, Tohami, Alaa & M. Hesham; All agreed that detail (A) is more efficient than detail (B)
Detail (A) shall be followed in all the projects until further notice and must be coordinated with Structure beams